What is the Tech Spec requirement for RCS leak detection when the reactor is critical and >2% power?

A

2 diverse RCS leak detection methods, including 1 sensitive to radiation, must be OPERABLE. If RM-A-2 is OOS, restore in 72 hours and sample every 8 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What actions are required if RM-A-9 is INOPERABLE?

A

Discontinue RB purge and CLOSE AH-V-1A/B/C/D within 8 hours. If purge valves can’t be CLOSED, Tech Spec 3.0.1 applies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the testing requirement for RB purge isolation valves and RM-A-9 when moving fuel in the RB?

A

They must be tested OPERABLE within 7 days of moving fuel in the RB.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Is the alarm pushbutton an accurate way to verify setpoints?

A

No, verify high alarm/alert setpoints by contacting I&C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens on a high RM-L-1 alarm?

A

MU-V-2A/B CLOSE, personnel in RCA are sent to RP checkpoint IAW C-1-1, and isolation occurs on HIGH alarm, not Low Scale. Letdown transport time is 30-60 minutes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What actions are required if RM-L-9 (ICCW) is rising and IC-T-1 level can’t be maintained on scale?

A

Trip the reactor, trip all 4 RCPs, CLOSE IC-V-2/3, and initiate AOP-050 RCS Leakage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does RM-L-12 monitor, and what happens on a high alarm?

A

IWTS/FS effluent local indication ONLY; AUTO CLOSES IW-V-73 release valve on high alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which radiation monitor is credited in the ODCM for terminating liquid rad releases?

A

RM-L-6 (near WECST).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens if RM-A-5/15 has 1 OPERABLE channel NOT restored within 14 days?

A

Tech Spec 3.0.1 applies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What interlocks come from the GAS channel high alarm?

A

“A pig only squeals when she has GAS.”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the sensitivity of RM-A-2 for RCS leakage detection?

A

RM-A-2 is sensitive to <1 gpm of RCS leakage and can detect within 1 hour to meet Tech Spec requirements.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What actions are required when working on RM-A-2?

A

Shut down the pump and isolate CM-V-1/4 to prevent violating containment integrity.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Does RM-A-2 require 8-hour sampling when out of service at HSD?

A

No, Tech Spec 3.1.6.8 is only required >2% power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens if RM-A-4 and RM-A-9 are in high alarm during fuel handling?

A

Trip AH-E-14s.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens on a high RM-A-6 alarm?

A

Trips AH-E-11 (supply) to ensure negative pressure and avoid unmonitored release.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What happens if RM-A-9 alarms during fuel movement?

A

Suspend fuel handling and evacuate personnel in RB, but do NOT terminate purge.

17
Q

What is the function of RM-A-14?

A

Pulls ESF slip stream using a 1C ESV sample pump.

18
Q

What happens if RM-A-7 is INOP during a gas release?

A

Continue the release if RM-A-8, AH-FT-149, and FT-150 are OPERABLE and capable of WDG-V-47 auto closure.

19
Q

What happens on a high RM-A-8 alarm?

A

Trips AH-E-10 and 11 and CLOSES WDG-V-47.

20
Q

What happens after 30 seconds of a gamma area monitor local alarm?

A

The horn resets, and the red beacon light starts and runs continuously.

21
Q

What happens if RM-G-7 fails LOW?

A

Terminate RB fuel moves until replaced with a portable instrument.

22
Q

What happens if RM-G-9 fails HIGH?

A

Terminate FHB fuel moves until replaced with a portable instrument. Trips AH-E-10 and isolates FHB dampers on high alarm.

23
Q

What happens on a high RM-G-16/17 alarm?

A

CLOSE CA-V-4/5 A/B.

24
Q

What happens on a high RM-G-18 alarm?

A

CLOSE CA-V-1, 2, 3, 13.

25
What manual action is required on a high RM-G-19 alarm?
CLOSE MU-V-25/26 (Seal Return/CBO line).
26
What happens on a high RM-G-20 alarm?
CLOSES WDL-V-303/304 and WDG-V-3/4.
27
What happens if detector voltage inside a rad monitor fails but the amplifier is still functional?
Interlocks remain functional.
28
What is the first indication of a transient?
RM-A-5/15, with RM-L-1 delayed by 30-60 minutes transport time.
29
Do interlocks actuate on HIGH alarm or alert?
Interlocks actuate on HIGH alarm, not alert.
30
What is the purpose of the DEFEAT switch when restoring a rad monitor to service?
Prevents auto actuation of interlocks on re-energization.
31
Which rad monitors are interlocked with AH-E-10 and FHB dampers?
RM-G-9 and RM-A-4.
32
Why is the RM-A-9 interlock defeated during fuel moves?
To ensure RB pressurization does NOT occur, preventing BWST gravity drain to RCS.
33
What actions are required on a high RM-A-2 alarm during fuel moves?
Evacuate RB, place fuel in an APPROVED location with grapple ENGAGED.
34