SUMPS AND WASTE COLLECTION SYSTEM Flashcards

(13 cards)

1
Q

What triggers the operation of WDL-P-2A/B pumps in the Fuel Handling Building sump?

A

They are automatically operated by level switches.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the maximum allowable level for the Aux Building sump, and why?

A

Do not exceed 3’ or 40% (6,000 gallons remaining) to ensure sufficient operator action time to isolate a leak in systems recirculating post-LOCA RB sump inventory.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where must the Aux Building sump be aligned before placing the RB sump on recirculation?

A

It must be aligned to the MWST per EOP-10.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens when the WDL-CE-201 combustible vapor monitor alarms?

A

It alarms on the H&V panel and closes WDL-V-529, 531, and 538.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What must be done with the SBO Diesel Sump before release?

A

It must be recirculated and sampled prior to release, with its normal discharge to IWTS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What action should be taken if an oil leak occurs in the Turbine Building sump?

A

Open SD-P-9A/B breakers to prevent automatic discharge to IWTS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the normal discharge destination for the Turbine Deluge pump (SD-P-5)?

A

It discharges to the river, with its breaker normally open to meet NPDES limits.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does LS-284A/B/C detect, and what action does it trigger?

A

It detects Turbine Building flood conditions (2/3) and automatically opens the roll-up door, triggering the trip of all CW pumps.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What prevents freezing in the Aux Boiler Sump discharge lines?

A

Solenoid-operated vacuum breaker valves drain the lines when the pump stops.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the purpose of SD-P-3A/B and SD-P-4A/B in the Intermediate Building sump?

A

They protect EFPs, with check valves closing if the Turbine Building floods to prevent backflow into the Intermediate Building.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Why are EDG building drains normally locked closed?

A

To prevent oil spills from entering the yard and flood water from damaging the EDGs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What triggers a leak alarm for MU, DH, and BS pump compartments?

A

A leak rate of 4.53 gpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where does the yard drainage system transfer water, and when is FO-V-74 opened?

A

It transfers water to the east dike, and FO-V-74 is maintained closed except during draining.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly