DIGITAL TURBINE CONTROL SYSTEM (DTCS) Flashcards

1
Q

What happens when the header pressure error exceeds 40# for 5 seconds?

A

The turbine bypasses DTCS and goes to HAND control.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the rate of change (R.O.C.) when the load set is adjusted in LOCAL?

A

The load reference increases at a rate of 5%/min.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does Mark V Limiting do to DTCS control?

A

It transfers DTCS to LOCAL control.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens when Mark V limiting conditions clear?

A

DTCS returns to REMOTE if it was previously in REMOTE.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the stator coolant parameters for DTCS?

A

Flow rate: 381-400 gpm; Outlet temperature: 80-82°C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What triggers Power Load Unbalance protection?

A

Turbine load exceeds generator load by 40%, and generator load changes by 100% in 35 milliseconds.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What sequence occurs during Power Load Unbalance actuation?

A

CVs and ICVs FAST CLOSE, load reference signal set to 3%, runs back at 150%/min, ICVs reopen after 1 second, CVs reopen after unbalance clears (<40%).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of Valve Position Limiting?

A

It prevents CVs from opening further than 105% of the setpoint.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the setpoint for Main Steam Pressure Limiting (MSPL)?

A

MSPL actuates on low main steam header pressure <800# and is normally disabled due to a non-redundant sensor.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens during Generator Closing Spurt?

A

Load auto increases to 2% at 50%/min for 5 seconds, then transfers to ICS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What triggers Intercept Valve actuation?

A

Leaders (1/3/5) positioned 10% above reference for 20-40% load rejection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens during Intercept Valve actuation?

A

All 6 IVs FAST CLOSE, valves released for speed control after 1 second.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the function of Mechanical/Electrical Lockout Valves during testing?

A

If a trip condition exists, the lockout valve is released to ensure the turbine trips.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens during Control Valve Testing?

A

First Stage Pressure Control (SPF) is active, sending a highly gained signal to the remaining 3 CVs to open and maintain 1st stage pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is required for Electrical Trip Solenoid valves to trip?

A

Both solenoid valves must be de-energized.