Q

What triggers the Pen Cooling fans to swap air supply?

A

Pen Cooling fans swap air supply based on inlet temperature sensed in the Turbine Building Air Shaft Temperature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What starts AH-E-15A/B (NS Area) fans?

A

AH-E-15A/B fans start on ES Block 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens to AH-E-8A (SFP Area) fans during an ES?

A

AH-E-8A fans are load shed on ES, while AH-E-8B remains unaffected.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What does RM-G-9 (SFP Bridge) trigger?

A

RM-G-9 trips AH-E-10 and closes FHB dampers.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens when AH-E-14s are lost?

A

Loss of AH-E-14s trips AH-E-10, AH-E-11, and AH-E-20A/B (Control Building Exhaust).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What causes ESF Ventilation inlet fire dampers (AH-D-64/74) to close?

A

AH-D-64/74 dampers close automatically on high temperature and high combustible vapors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens when AH-E-14B/D trips?

A

A trip of AH-E-14B/D causes AH-E-10 and AH-E-11 to trip.