VENTILATION - AUX AND FUEL HANDLING BUILDING Flashcards
(7 cards)
What triggers the Pen Cooling fans to swap air supply?
Pen Cooling fans swap air supply based on inlet temperature sensed in the Turbine Building Air Shaft Temperature.
What starts AH-E-15A/B (NS Area) fans?
AH-E-15A/B fans start on ES Block 4.
What happens to AH-E-8A (SFP Area) fans during an ES?
AH-E-8A fans are load shed on ES, while AH-E-8B remains unaffected.
What does RM-G-9 (SFP Bridge) trigger?
RM-G-9 trips AH-E-10 and closes FHB dampers.
What happens when AH-E-14s are lost?
Loss of AH-E-14s trips AH-E-10, AH-E-11, and AH-E-20A/B (Control Building Exhaust).
What causes ESF Ventilation inlet fire dampers (AH-D-64/74) to close?
AH-D-64/74 dampers close automatically on high temperature and high combustible vapors.
What happens when AH-E-14B/D trips?
A trip of AH-E-14B/D causes AH-E-10 and AH-E-11 to trip.