What action is required if the number of COPs is reduced to 1 with only 1 booster pump and 1 FW pump?

A

Ensure plant load is reduced to <50% (OP-TM-421-000).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the minimum required CST level per T.S. 3.4.1.1(c)?

A

CSTs require >150,000 gallons each (11 ft).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the restoration timeline if one CST is INOPERABLE?

A

Restore in 72 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What actions are required if both CSTs are INOPERABLE?

A

Be subcritical in 1 hour, HSD in 6 hours, and CSD in 6 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the secondary coolant activity limit for I-131?

A

≤0.10μCi/g or go to HSBY in 6 hours.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the trip and start permissive pressure for condensate booster pumps?

A

Trip at 3# oil pressure, start permissive at 6#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What triggers the auto start of Booster Pump Aux Oil Pumps (CO-P-9A/B/C)?

A

Auto start when the pump is taken out of PTL or pressure drops to 5#.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens to CO-P-9A/B/C at 12# pressure?

A

They trip (shaft driven).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the impact of losing “B” DC on the counting circuit?

A

Prevents auto start and trip of pumps and no remote CO-P-2 starts.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What sequence do CO-P-2 pumps follow during startup?

A

They always start in A-B-C sequence.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What happens to CO-V-6 (Hotwell Reject) on high hotwell level?

A

It OPENS to reject water to CSTs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens to CO-V-6 on high CST level?

A

It CLOSES.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the function of CO-V-7 (Normal MU)?

A

Maintains normal hotwell level and closes during emergency lineup.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the function of CO-V-8 (Emergency MU)?

A

Vacuum drags makeup water to CST directly, opens during emergency lineup.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What happens to CO-V-6, CO-V-7, and CO-V-8 on loss of air?

A

CO-V-6 fails CLOSED, CO-V-7/8 fail OPEN.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the function of CO-V-51?

A

Bypasses Powdex, fails OPEN on loss of air, opens at 35psid rising and fully opens at 50psid.

17
Q

When does CO-V-5 (Booster Pump Recirc) open?

A

Opens when CO <3000gpm and discharge pressure >100#.

18
Q

What is the purpose of CO-V-5?

A

Protects the pump string and prevents draining the heater.

19
Q

What is the function of CO-T-9 (Condensate Head Tank)?

A

It is AUTO filled from CO-P-2 discharge and supplies condenser vacuum seals, with vacuum pump seals tapping off before the head tank.

20
Q

What action should be taken for emergency NS-T-1 makeup if DW-P-1 is unavailable and NS-T-1 level is lowering?

A

OPEN CO-V-170.

21
Q

What happens if CO-FE-9 fails low?

A

CO flow will increase, the recirculation valve will OPEN, and the discharge pressure of the booster pumps will decrease (higher flow).

22
Q

What is the restoration requirement if both CO-T-1A/B level transmitters are INOPERABLE?

A

They must be restored within 7 days.